Schematic MCB time–current tripping curve on logarithmic axes, showing the common thermal overload region and the instantaneous magnetic trip zones for Type B (3–5×In), Type C (5–10×In) and Type D (10–20×In), per IS/IEC 60898.

The plain-language note on MCBs covers what the device does and how to read the letter and the number on its face. This is the engineer's companion: the time–current characteristic itself, how to read the curve, exactly where Types B, C and D each belong and where they fall short, and what the kA rating is for.

Reading the time–current curve

An MCB's behaviour is defined by a curve plotted on logarithmic axes: the multiple of rated current (× In) along the bottom, and the time to trip up the side. The curve has two regions, produced by two independent mechanisms inside the breaker:

Two further points. The characteristic is a band, not a single line, manufacturing tolerance and whether the breaker starts hot or cold shift the exact trip time. And the thermal region is essentially the same for B, C and D of a given rating; the only thing the type changes is where the magnetic region begins.

The thermal region, the IS gate points

IS/IEC 60898 pins the thermal characteristic to fixed test points, identical across the three types. These are the numbers the curve must honour:

Test currentRequired behaviourWithin
1.13 × InMust not tripThe conventional time (1 hour, for In ≤ 63 A)
1.45 × InMust tripThe conventional time (1 hour)
2.55 × InMust tripBetween 1 s and 60 s (for In ≤ 32 A)

In plain terms, an MCB is expected to carry roughly 1.13 × its rating indefinitely and to clear a modest sustained overload within the hour. It is deliberately unhurried here, a brief overload, such as a few heavy appliances coinciding for a minute, should not trip a healthy circuit.

The magnetic region, where B, C and D differ

The type letter sets the current at which the instantaneous magnetic trip takes over. That is the entire difference between B, C and D:

TypeInstantaneous tripBuilt for
B3 – 5 × InResistive and low-inrush loads; long cable runs
C5 – 10 × InGeneral mixed loads, the everyday default
D10 – 20 × InHigh-inrush loads, motors, transformers, capacitor banks

Below its band the device can still trip, but only on the slower thermal element; at or above the upper figure it trips instantaneously. So the choice of type balances two things at once, the load's switch-on inrush, and the fault current available at that point in the installation.

B, C and D, where each belongs, and where it doesn't

Type B, 3 to 5 × In

Type C, 5 to 10 × In

Type D, 10 to 20 × In

The thread through all three: a lower type (B) trips on a smaller fault and is easier to satisfy on long, low-fault runs, but tolerates little inrush; a higher type (D) tolerates heavy inrush but needs a strong fault current to act instantaneously. C sits in the middle, which is why it is the everyday answer.

The kA rating, breaking capacity

The type and the rating describe how the MCB responds to overcurrent. The kA rating describes something separate: the largest short-circuit current the breaker can interrupt safely, clearing the fault without damage to itself. It is independent of the curve.

The rule is simply that the breaker's Icn must exceed the prospective fault current at the point where it is installed. That fault current is highest close to the source, at the incomer, near the transformer or the supply MCCB, and falls as cable impedance accumulates downstream. So a main or upstream MCB is commonly specified at 10 kA, while a breaker deep in residential sub-distribution may be safely served by 6 kA. Where an upstream device shares the duty, a documented back-up (cascading) coordination can let a lower-kA MCB sit behind a higher-rated breaker, but only where the manufacturer's tables confirm the pairing.

Specifying an MCB, in three independent choices

Put together, every MCB is three separate decisions:

Get those three right and the curve does the rest, exactly as the chart above describes.

What we stock

Shreetuvis stocks the full MCB ladder in Nagpur, Hager and Legrand DX³, across 6 to 63 A, curves B, C and D, breaking capacities of 6 kA and 10 kA, and single- to four-pole, ISI-marked to IS 8828 (see the ISI mark) and supplied genuine from the authorised channel. See the Hager MCB page for the range, or send a circuit schedule through the contact form for stock and project-rate pricing. For the plain-language version, see MCBs, the switches in your board; the device that partners it on every board is the RCCB.